+38 (044) 206-69-00 [email protected]
  • Русский
  • English
  • Українська
Categories

Device DDO-24 – 5A АИАР.426449.002

Device DDO-24 - 5A АИАР.426449.002 4386
Device DDO-24 - 5A АИАР.426449.002 4387
Device DDO-24 - 5A АИАР.426449.002 4388

The device DDO-24 is intended for data exchange via three-wire serial RS485 interface lines with the Modbus RTU exchange protocol and for issuing commands received via the interface by closing dry contacts of the relay. The device DDO-24 can be used in various automated monitoring and control systems.

Specifications

  • Number of discrete output channels - 24 channels with galvanic isolation, "dry" relay contacts.
  • The dielectric strength of the discrete output channels and power inputs is 1.5 kV.
    • The switching capacity of the relay contacts is as follows:
    • when the circuits are closed - 250 V, 5 A, 1000 VA / W;
    • when AC circuits are opened - 250 V, 5 A, 1000 VA / W;
    • when opening DC circuits up to 30 V - 5 A;
    • when opening DC circuits up to 125 V - at least 50 W;
    • continuous current 5 A.
  • The device is powered from a constant current source with a voltage of 7 to 40 V.
  • Power consumed by the device from a DC source - no more than 5.5 W.
  • In the event of a main power failure, there is a backup power supply input with the same parameters.
  • Resistance to short-term interruption of the supply voltage, not less than 0.5 s.
  • The time the device is ready for operation after the supply voltage is applied to it, no more than 0.5 s
  • DDO-24 weight - no more than 350 g.
  • The DDO-24 device is designed for mounting on a DIN rail.
  • Information transfer is carried out through the RS485 interface using the Modbus RTU exchange protocol.
  • Ethernet interface (RJ-45) - IEC 60870-5 104 exchange protocol (optional).

Software Wisinet2 for МРЗС-05Л, МРЗС-05Д, MRZS

Please pay attention! Many new versions of devices have been added for corrective work, the program must save the /data folder (with your archives), delete the WisiNet2 installation program, download the archive from the website and install the Wisinet2 program and replace the new /data folder with your previous oneDownload Wisinet 2