Categories
Disposing device ДШ AИAР. 468243.002
The ДШ device is designed to control maximum current relays of types РТМ, РТМТ, РТВ and РТВТ.
The rated current of the current circuit of the device is DSH - 5 A.
The number of bypass/re-bypass channels - 2 (phases A and C).
Range of bypass currents - from 1,5 to 150 A.
- at a current of 1.5 A - not less than 1 and not more than 560 Ohm,
- at a current of 50 A - not more than 20 Ohm,
- at a current of 150 A - not more than 7 Ohm.
- The maximum value of the current at which the technical characteristics of the device are provided is not more than:
- long 5 A
- within 5 minutes 8 A
- within 5 seconds 75 A
- within 1 second of 150 A.