Central annunciator units MRZS-O

The device is intended for the organization of central signaling systems at substations, stations, and industrial facilities equipped with microprocessor-based, electronic, or electromechanical relay protection and automation devices.

It performs the following functions:

  • monitoring and recording of discrete input signals, including pulse signals;
  • monitoring and recording of group signaling input signals;
  • generation of discrete output signals;
  • monitoring of audio-visual signaling status;
  • receiving and displaying alarm and warning signals with or without time delay;
  • visual indication of input states;
  • control of sound signaling (up to seven sound signaling devices) with automatic acknowledgment capability;
  • transmission of signals to group signaling;
  • transmission of signals to external visual signaling devices, including flashing mode;
  • communication with higher-level control, data transmission and reception of signals with the ability to affect internal logic, LEDs, relays, acknowledgment.

Number of inputs

  • 28–56 freely programmable discrete inputs
  • 0–4–8 inputs with current increment measurement for group signaling (GSS)
  • 0–1–2 analog inputs for control of operating voltage value - operation by current in the device does not depend on voltage level (GSS operation by resistance).

Number of LEDs

  • 60 freely programmable single-color
  • 2 service three-color LEDs:
    • device healthy/faulty status
    • sound signaling operation

Number of discrete outputs – 9

  • 7 relay outputs
  • 2 power outputs
  • all outputs freely programmable, including pulsing light relay

Buttons

  • 3 service buttons: sound signaling off button “Silence”, indication reset button, LED test button
  • 4 freely programmable buttons
  • 6 navigation buttons
  • Discrete event recorder – event log up to 200,000 entries with recording of: discrete input states; group signaling function outputs; functional buttons; outputs of internal logic elements; input and output GOOSE messages; input and output MMS messages; telecontrol signals; outputs of other functions
  • Digital oscilloscope of operating voltage inputs: up to 5 s before the fault, fault process, and up to 25 s after the fault. Total recording length – at least 160 s.
    • Free programmable logic

      Interfaces: RS-485, USB, Ethernet (RJ-45 or optical ST);

      Communication protocols: Modbus RTU, Modbus TCP, IEC 61850 (GOOSE, MMS), DNP3, IEC 60870-5-103, IEC 60870-5-104

      Multilingual menu – supports 3 languages.

    Software WisiNet_2 for МРЗС-05Л, МРЗС-05Д, MRZS

    Please pay attention! Many new versions of devices have been added for corrective work, the program must save the /data folder (with your archives), delete the WisiNet2 installation program, download the archive from the website and install the Wisinet2 program and replace the new /data folder with your previous oneDownload Wisinet 2