Device DDIО-24 AИAР.426449.004-01

Device DDIО-24  AИAР.426449.004-01 10319

Device DDIO-24 can be used in various automated monitoring and control systems. Device DDIO-24 is intended for input of discrete electrical signals for their processing and data exchange via three-wire serial RS485 interface lines with Modbus RTU protocol and exchange via three-wire serial RS485 interface lines with the Modbus RTU exchange protocol and for issuing commands received via the interface by closing "dry" contacts of the relay.

Specifications:

  • Number of digital input channels - 12 channels with galvanic isolation.
  • The dielectric strength of the isolation of the discrete input channels and power inputs is 1.5 kV.
  • Type of voltage on the discrete input channel - DC or AC.
  • The maximum allowable voltage on the digital input channel is 250 V.
  • The “logic zero” level is from 0 to 11V, the “logic one” level is from 17 V to 24 V.
  • Number of discrete output channels - 12 channels with galvanic isolation, "dry" relay contacts.
  • The dielectric strength of the discrete output channels and power inputs is 1.5 kV.
  • The switching capacity of the relay contacts is as follows:
  • when the circuits are closed - 250 V, 5 A, 1000 VA / W;
  • when AC circuits are opened - 250 V, 5 A, 1000 VA / W;
  • when opening DC circuits up to 30 V - 5 A;
  • when opening DC circuits up to 125 V - at least 50 W;
  • continuous current 5 A.
  • The device is powered from a constant current source with a voltage of 7 to 40 V.
  • Power consumed by the device from a DC source - no more than 5.5 W.
  • In the event of a main power failure, there is a backup power supply input with the same parameters.
  • Resistance to short-term interruption of supply voltage, not less than 0.5 s
  • The time the device is ready for operation after the supply voltage is applied to it, no more than 0.5 s
  • DDIO-24 weight - no more than 330 g.
  • The DDIO-24 is designed for DIN rail mounting.
  • Information transfer is carried out through the RS485 interface using the Modbus RTU exchange protocol.
  • Ethernet interface (RJ-45) - IEC 60870-5 104 exchange protocol (optional);